Actuator selection data
Thermal current, continuous
Minimum load voltage / current
Short-circuit current to IEC 947-5-1
Switching capacity and service life of contacts
with resistive load
Voltage
24 V DC
60 V DC
120 V DC
24 V AC
48 V AC
60 V AC
120 V AC
230 V AC
with inductive load to IEC 947-5-1 DC13/AC15
Voltage
24 V DC
DC 60 V
DC 120 V
24 V AC
48 V AC
AC 60 V
AC 120 V
230 V AC
An external protective circuit will increase the service life of contacts.
Size of the motor starter
Lamp load
Contact protection (internal)
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
3.33 Relay output module SM 322; DO 16 x Rel. AC 120/230 V; (6ES7322-1HH01-0AA0)
max. 2 A
10 V / 10 mA
200 A, with B10/B16 circuit breaker
Current
No. of switching cycles (typical)
2.0 A
0.1 million
1.0 A
0.2 million
1.0 million
0.5 A
0.5 A
0.2 million
0.2 A
0.6 million
1.5 A
1.5 million
1.5 A
1.5 million
1.5 A
1.5 million
2.0 A
1.0 million
1.0 A
1.5 million
0.5 A
2.0 million
1.0 million
2.0 A
1.0 A
1.5 million
0.5 A
2.0 million
Current
No. of switching cycles (typical)
2.0 A
0.05 million
1.0 A
0.1 million
0.5 A
0.5 million
0.5 A
0.1 million
0.2 A
0.3 million
1.5 A
1 million
1.5 A
1 million
1.5 A
1 million
2.0 A
0.7 million
1.0 A
1.0 million
0.5 A
1.5 million
2.0 A
0.7 million
1.0 A
1.0 million
0.5 A
1.5 million
max. size 5 to NEMA
50 W / 230 V AC
5 W / 24 V DC
none
Digital modules
201

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data