Programmable Parameters - Siemens SIMATIC Manual

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Analog modules
6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0)
6.4.2

Programmable parameters

Introduction
For information on programming analog modules, refer to the chapter Programming analog
modules (Page 294).
Parameter
Table 6- 11
Overview of parameters of SM 331; AI 8 x 16 Bit
Parameters
Enable
Process interrupt when limit value
is exceeded
Process interrupt at end of cycle
Diagnostics interrupt
Process interrupt trigger
High limit
Low limit
Diagnostics
Group diagnostics
Line continuity check
Measurement
Module operating mode
Noise suppression
Smoothing
Measurement type
disabled
Voltage
Current (4-wire transducer)
See also
Diagnostics messages of analog input modules (Page 296)
Programming analog modules (Page 294)
324
Range of values
yes/no
yes/no
yes/no
32511 to -32512
-32512 to 32511
yes/no
yes/no
8 channels
4 channels
50 Hz
60 Hz
400 Hz
50/60/400 Hz
none
weak
medium
strong
Measuring range:
± 5 V
1 V to 5 V
± 10 V
0 mA to 20 mA
4 mA to 20 mA
± 20 mA
Defaults
Parameter type
no
dynamic
no
dynamic
no
dynamic
-
dynamic
-
dynamic
no
static
no
yes
dynamic
no
50/60/400 Hz
none
dynamic
dynamic
± 10 V
4 mA to 20 mA
Scope
Module
Channel
Channel
Channel
Channel
Module
Channel group
Channel group
Channel group
S7-300 Module data