Siemens SIMATIC Manual page 271

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Representation of analog values for Cu 10 climatic and Cu 10, 50, 100 GOST climatic resistance
thermometers
Table 5- 19
Representation of analog values for Cu 10 climatic and Cu 10, 50, 100 GOST climatic resistance thermome-
ters
Cu x0 cli-
Units
matic/in °C
dec
(1 digit =
0.01 °C)
> 180.00
32767
180.00
18000
:
:
150.01
15001
150.00
15000
:
:
-50.00
-5000
-50.01
-5001
:
:
-60.00
-6000
< - 60.00
-32768
Representation of analog values for Cu 10, 50, 100, 500 GOST standard (0.00426) resistance
thermometers
Table 5- 20
Representation of analog values for Cu 10, 50, 100, 500 GOST standard (0.00426) resistance thermometers
Cu x0
Units
Standard in
dec
hex
°C (1 digit =
0.1°C)
> 240.0
32767
7FFF
240.0
2400
0960
:
:
:
200.1
2001
07D1
200.0
2000
07D0
:
:
:
-50.0
-500
FE0C
-50.1
-501
FE0B
:
:
:
-60.0
-600
FDA8
< - 60.00
-32768
8000
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
Cu x0 cli-
matic in °F
hex
(1 digit =
0.01 °F)
7FFF
> 327.66
H
4650
327.66
H
:
:
3A99
280.01
H
3A98
280.00
H
:
:
EC78
- 58.00
H
EC77
-58.01
H
:
:
E890
-76.00
H
8000
< - 76.00
H
Cu x0 stan-
Units
dard in °F
dec
(1 digit =
0.01 °F)
> 464.0
32767
H
464.0
4640
H
:
:
392.1
3921
H
392.0
3920
H
:
:
-58.0
-580
H
-58.1
-581
H
:
:
-76.0
-760
H
< - 76.0
-32768
H
5.1 Representation of the values for analog input channels
Units
Range
dec
hex
32767
7FFF
Overflow
H
32766
7FFE
Overshoot range
H
:
:
28001
6D61A
H
28000
6D60
Rated range
H
:
:
-5800
E958
H
-5801
E957
Undershoot range
H
:
:
-7600
E250
H
-32768
8000
Underflow
H
Range
hex
7FFF
Overflow
H
1220
Overshoot range
H
:
0F51
H
0F50
Rated range
H
:
FDBC
H
FDBB
Undershoot range
H
:
FD08
H
8000
Underflow
H
Principles of analog modules