3.29 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0)
3.29.3

SM 322; DO 8 x DC 24 V/0.5 A - Behavior

Influence of the operating state and supply voltage on output values
The output values of SM 322; DO 8 x DC 24V/0.5 A are determined by the CPU's operating
state and the module's power supply.
Table 3- 31
Influence of the CPU operating state and of the supply voltage L+ of SM 322; DO 8 24 VDC/0.5 A on output
values.
CPU
operating state
POWER ON
RUN
STOP
POWER OFF
-
Reaction to power failure
Failure of the power supply to SM 322; DO 8 x DC 24V/0.5 A is always indicated at the
module's SF LED. This information is also available on the module (entry in diagnostics
data.)
Triggering of diagnostics interrupts is determined by the parameter settings (see the next
chapter Interrupts of SM 322; DO 8 x DC 24/0.5 A (Page 182)).
See also
SM 322; DO 8 x DC 24 V/0.5 A - Parameters (Page 178)
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
Power supply L+ at digital module
L+ present
L+ missing
L+ present
L+ missing
L+ present
L+ missing
Digital modules
Output value
of the digital module
CPU value
0 signal
Substitute value/last value (default = 0
signal)
0 signal
0 signal
0 signal