Analog modules
6.14 Analog output module SM 332; AO 4 x 12 Bit; (6ES7332-5HD01-0AB0)
6.14.2
Programmable parameters
Introduction
For general information on programming analog modules, refer to the chapter Programming
analog modules (Page 294).
The table below provides overview of programmable parameters and of their defaults.
Table 6- 37
Overview of the parameters of SM 332; AO 4 x 12 Bit
Parameters
Enable
•
Diagnostic interrupt
Diagnostics
•
Group diagnostics
Output
•
Output type
•
Output range
Reaction to CPU STOP ASS
Assigning parameters to channels
The parameters can be set separately at each output channel of SM 332; AO 4 x 12 Bit. You
can assign separate parameters to each output channel.
Assign the parameters you set at the SFCs in the user program to the channel groups. Each
output channel of SM 332; AO 4 x 12 Bit is thus assigned to a channel group, i.e. output
channel 0 > channel group 0, for example.
Note
The output may carry incorrect interim values if you modify output ranges while SM 332; AO
4 x 12 Bit is in RUN.
See also
Diagnostic messages of analog output modules (Page 296)
466
Range of values
yes/no
yes/no
disabled
Voltage
Current
Output ranges for SM 332;
See table of
AO 4 x 12 Bit
Outputs zero current/voltage
HLV
Hold last value
SSV
Set substitute value
Default
Parameter
type
no
dynamic
no
static
V
dynamic
± 10 V
ASS
dynamic
Manual, 06/2017, A5E00105505-AJ
Scope
Module
Channel
Channel
Channel
S7-300 Module data