6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0)
Technical specifications
Generation of analog values
Measuring principle
Integration/conversion time/resolution (per channel)
programmable
Basic conversion time per channel
Resolution (including overshoot range)
Interference frequency suppression at interference fre-
quency f1 in Hz
Basic execution time of the module (independent of the
number of enabled channels)
Interference frequency suppression, error limits
Interference frequency suppression at f = n (f1 ± 1 %), (f1 = interference frequency) n=1.2...
Common mode interference (CMV < 11 Vpp)
Series-mode interference (peak value < rated input range)
Crosstalk between inputs
Operational limit (across entire temperature range, relative to measurement range end value in the selected input range)
Voltage input
Current input
Basic error limit (operational limit at 25 °C, relative to the measurement range end value in the selected input range)
Voltage input
Current input
Temperature error (relative to input range)
Linearity error (relative to input range)
Repeat accuracy (in settled state at 25 °C, relative to input
range)
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
Actual value conversion
yes
52 µs
14 bits
none
400
0.42 ms
2.5 ms
> 80 dB
> 40 dB
> 65 dB
± 1 V
± 5 V
± 10 V
1 V to 5 V
± 20 mA
0 mA to 20 mA
4 mA to 20 mA
± 1 V
± 5 V
± 10 V
1 V to 5 V
± 20 mA
0 mA to 20 mA
4 mA to 20 mA
± 0.004 %/K
± 0.03 %
± 0.1 %
Analog modules
60
50
16.7 ms
20 ms
± 0.3 %
± 0.4 %
± 0.3 %
± 0.4 %
± 0.3 %
± 0.3 %
± 0.3 %
± 0.2 %
± 0.25 %
± 0.2 %
± 0.25 %
± 0.2 %
± 0.2 %
± 0.2 %
333