Analog modules
6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0)
6.3.2
Programmable parameters
Introduction
For information on programming analog modules, refer to the chapter Programming analog
modules (Page 294).
Parameters
Table 6- 6
Overview of the parameters of SM 331; AI 8 x 16 Bit
Parameters
Enable
•
Diagnostic interrupt
•
Hardware interrupt when
limit exceeded
Hardware interrupt trigger
•
High limit
•
Low limit
Diagnostics
•
Group diagnostics
•
with line continuity check
Measurement
•
Measurement type
•
Measuring range
•
Noise suppression
Channel groups
The channels of SM 331; AI 8 x 16 Bit are arranged in four groups of two channels. You can
assign parameters only to one channel group.
314
Range of values
yes/no
yes/no
May be restricted by the measuring range.
from 32511 to - 32512
from - 32512 to 32511
yes/no
yes/no
disabled
Voltage V:
4DMU current (4-wire transducer)
See the table
Measurement types and ranges
100 Hz; 60 Hz; 50 Hz; 10 Hz
Default
Parameter
type
no
dynamic
no
-
dynamic
no
static
no
V
dynamic
± 10 V
50 Hz
Manual, 06/2017, A5E00105505-AJ
Scope
Module
Channel
Channel
group
Channel
group
S7-300 Module data