Programmable Parameters - Siemens SIMATIC Manual

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Analog modules
6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0)
6.3.2

Programmable parameters

Introduction
For information on programming analog modules, refer to the chapter Programming analog
modules (Page 294).
Parameters
Table 6- 6
Overview of the parameters of SM 331; AI 8 x 16 Bit
Parameters
Enable
Diagnostic interrupt
Hardware interrupt when
limit exceeded
Hardware interrupt trigger
High limit
Low limit
Diagnostics
Group diagnostics
with line continuity check
Measurement
Measurement type
Measuring range
Noise suppression
Channel groups
The channels of SM 331; AI 8 x 16 Bit are arranged in four groups of two channels. You can
assign parameters only to one channel group.
314
Range of values
yes/no
yes/no
May be restricted by the measuring range.
from 32511 to - 32512
from - 32512 to 32511
yes/no
yes/no
disabled
Voltage V:
4DMU current (4-wire transducer)
See the table
Measurement types and ranges
100 Hz; 60 Hz; 50 Hz; 10 Hz
Default
Parameter
type
no
dynamic
no
-
dynamic
no
static
no
V
dynamic
± 10 V
50 Hz
Manual, 06/2017, A5E00105505-AJ
Scope
Module
Channel
Channel
group
Channel
group
S7-300 Module data

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data