Siemens SIMATIC Manual page 488

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Analog modules
6.17 Analog IO module SM 334; AI 4/AO 2 x 12 bit; (6ES7334-0KE00-0AB0)
Technical specifications
Interference frequency suppression, error limits for inputs
Interference frequency suppression at F = n (f1 ± 1 %) (f1 = interference frequency)
Common mode interference (V
Seriesmode interference (peak interference value < rated input
range)
Crosstalk between inputs
Operational limit (across entire temperature range, relative to the measurement range end value in the selected input
range)
Voltage input
Resistance input
Temperature input
Basic error limit (operational limit at 25 °C, relative to the measurement range end value in the selected input range)
Voltage input
Resistance input
Temperature input
Temperature error (relative to input range)
Linearity error (relative to input range)
Repeat accuracy (in settled state at 25 °C, relative to input range)
Interference frequency suppression, error limits of outputs
Crosstalk between outputs
Operational limit (across entire temperature range, relative to measurement range end value in the selected output range)
Voltage output
Basic error limit (operational limit at 25 °C, relative to the measurement range end value in the selected output range)
Voltage output
Temperature error (relative to output range)
Linearity error (relative to output range)
Repeat accuracy (in transient state at 25 °C, relative to output range) ± 0.01 %
Output ripple; range 0 Hz to 50 kHz (relative to output range)
Status, interrupts, diagnostics
Interrupts
Diagnostic function
Encoder selection data
Input ranges (rated values) / input impedance
Voltage
Resistance
Temperature
Maximum voltage at voltage input (destruction limit)
488
< 1 V)
pp
> 38 dB
> 36 dB
> 88 dB
0 V to 10 V
10 kΩ
Pt 100
0 V to 10 V
10 kΩ
Pt 100
± 0.01 %/K
±0.05 %
± 0.05 %
> 88 dB
± 1.0 %
± 0.85 %
± 0.01 %/K
± 0.01 %
± 0.1 %
none
none
0 V to 10 V
10 kΩ
Pt 100
max. 20 V continuous; 75 V for max. duration of 1 s
(duty factor 1:20)
Manual, 06/2017, A5E00105505-AJ
± 0.7 %
± 3.5 %
± 1 %
±0.5 %
± 2.8 %
± 0.8 %
100 kΩ
10 MΩ
10 MΩ
S7-300 Module data

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data

Table of Contents