Representation of analog values for KTY84/130 silicon temperature sensors
Table 5- 23
Representation of analog values for KTY84/130 silicon temperature sensors
KTY84/130
Units
in °C
dec
(1 digit = 0.1
°C)
> 352.8
32767
352.8
3528
:
:
300.1
3001
300
3000
:
:
-40
-400
-40.1
-401
:
:
-47.0
-470
< -47.0
-32768
Representation of the analog values of thermocouples type B
Table 5- 24
Representation of the analog values of thermocouples type B
Type B
Units
in °C
dec
> 2070.0
32767
2070.0
20700
:
:
1820.1
18201
1820.0
18200
:
:
0.0
0
:
:
-120.0
-1200
< -120.0
-32768
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
KTY84/130
Units
in °F
hex
dec
(1 digit =
0.1 °F)
7FFF
> 667.0
32767
H
0DC8
667.0
6670
H
:
:
:
0BB9
572.1
5721
H
0BB8
572
5720
H
:
:
:
FE70
-40
-400
H
FE6F
-40.1
-401
H
:
:
:
FE2A
-52.6
-526
H
8000
< -52.6
-32768
H
Type B in
Units
°F
hex
dec
7FFF
> 3276.6
32767
H
50DC
3276.6
32766
H
:
:
:
4719
2786.6
27866
H
4718
2786.5
27865
H
:
:
:
0000
32.0
320
H
:
:
:
FB50
-184.0
-1840
H
8000
< -184.0
-32768
H
5.1 Representation of the values for analog input channels
KTY84/130
in °K
hex
(1 digit =
0.1 °K)
7FFF
> 626.0
H
1A0E
626.0
H
:
:
1659
573.3
H
1658
573.2
H
:
:
FE70
233.2
H
FE6F
233.1
H
:
:
FDF2
226.2
H
8000
< 226.2
H
Type B in K
hex
7FFF
> 2343.2
H
7FFE
2343.2
H
:
:
6CDA
2093.3
H
6CD9
2093.2
H
:
:
0140
273.2
H
:
:
F8D0
153.2
H
8000
< 153.2
H
Principles of analog modules
Units
Range
dec
hex
32767
7FFF
Overflow
H
6260
1874
Overshoot
H
range
:
:
5733
1665
H
5732
1664
Rated range
H
:
:
2332
091C
H
2331
091B
Undershoot
H
range
:
:
2262
08D6
H
-32768
8000
Underflow
H
Units
Range
dec
hex
32767
7FFF
Overflow
H
23432
5B88
Overshoot
H
range
:
:
20933
51C5
H
20932
51C4
Rated range
H
:
:
2732
0AAC
H
:
:
Undershoot
range
1532
05FC
H
32768
8000
Underflow
H
273