Digital modules
3.27 Digital output module SM 322; DO 16 x AC 120/230 V/1 A; (6ES7322-1FH00-0AA0)
SM 322; DO 16 x AC 120/230 V/1 A - Technical specifications
Technical specifications
Dimensions and weight
Dimensions W x H x D
Weight
Module-specific data
Supports isochronous mode
Number of outputs
Cable length
•
unshielded
•
shielded
Voltages, currents, electrical potentials
Load voltage L1
All load voltages must be connected to the same phase
Total current of outputs (per group)
•
horizontal mounting position
to 40 °C
to 60 °C
•
vertical mounting position
to 40 °C
Electrical isolation
•
between channels and the backplane bus
•
between channels
in groups of
Maximum potential difference
•
between M
and outputs
internal
•
between outputs of different groups
Isolation test voltage
Current consumption
•
from the backplane bus
•
from load voltage L+ (no-load)
Power loss of the module
Status, interrupts, diagnostics
Status display
Interrupts
•
Diagnostic interrupt
Diagnostic functions
•
Group error display
168
40 x 125 x 117
ca. 275 g
No
16
max. 600 m
max. 1000 m
120/230 VAC
max. 4 A
max. 2 A
max. 2 A
yes
yes
8
230 VAC
500 VAC
4000 VDC
max. 200 mA
max. 2 mA
typ. 8.6 W
green LED per channel
no
red LED (SF)
(fuse or no L1/N)
Manual, 06/2017, A5E00105505-AJ
S7-300 Module data