Siemens SINAMICS S120 Manual page 183

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Article number
Dimensions
- Width
- Height
- Depth
Frame size
Weight, approx.
Recommended fuse
2)
- Number per phase (connected in parallel)
- Rated current
- Frame size acc. to IEC 60269
Minimum short-circuit current
The specified power loss is the maximum value at 100% capacity utilization. The value in normal operation is lower.
1)
To achieve a UL-approved system, it is absolutely essential to use the fuse types specified in the table.
2)
Minimum current required for reliable triggering of the protective devices.
3)
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
6SL3330–
6TE35–5AA3
mm
310
mm
1420
mm
550
GX
kg
150
3NE1435-2
1
560
3
kA
6.2
3)
5.3 Smart Line Modules
6TE37–3AA3
6TE41–1AA3
310
503
1420
1475
550
550
GX
HX
150
294
3NE1437-2
3NE1334-2
1
2
710
500
3
3
9.2
10.4
Line Modules
6TE41–3AA3
704
1480
550
JX
458
3NE1436-2
2
630
3
16
181

Advertisement