Safety Information - Siemens SINAMICS S120 Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-side power components
4.2 Line filters for Basic Line Modules
Basic Line Module
6SL3330-1TG33-3AA3
6SL3330-1TG34-3AA3
6SL3330-1TG36-8AA3
6SL3330-1TG41-1AA3
6SL3330-1TG41-4AA3
6SL3330-1TG41-8AA3
If a Motor Module Chassis-2 is not connected to the DC link, then line filter 6SL3000-0BE41-6AA0 can be used when the
1)
device is deployed in category C2 (first and second environment).
If a Motor Module Chassis-2 is connected to the DC link, then the line filter 6SL3760-0MR00-0AA0 must be used when
2)
used in category C2 (first and second environment).
4.2.2

Safety information

Not observing fundamental safety instructions and residual risks
Not observing fundamental safety instructions and residual risks listed in Chapter 1 can
result in accidents with severe injuries or death.
• Comply with the fundamental safety instructions.
• When assessing the risk, take into account remaining risks.
Burns resulting from high surface temperatures
The line filter can become very hot. Contact with the surface can result in severe burns.
• Mount the line filter so that contact is not possible. If this is not possible, attach a clearly
• To prevent adjacent components from suffering damage due to these high
NOTICE
Line filter damage by connecting to impermissible line supplies
The line filters are only suitable for direct connection to TN or TT systems with grounded
neutral point. Line filters are designed for connection to systems with a continuous level to
voltage harmonics in accordance with EN 61000-2-4, Class 3. Connection of the line filter to
other line systems may result in damage.
• Only connect the line filter to TN or TT systems with grounded neutral point and a
48
Rated power of the Basic Line Module
Line voltage 500 – 690 V 3 AC
WARNING
CAUTION
visible and understandable warning notice at hazardous positions.
temperatures, maintain a clearance of 100 mm on all sides of the line filter.
continuous level of voltage harmonics in accordance with EN 61000-2-4, Class 3.
250 kW
355 kW
560 kW
900 kW
1100 kW
1500 kW
Suitable line filter
6SL3000-0BG34-4AA0
6SL3000-0BG34-4AA0
6SL3000-0BG36-0AA0
6SL3000-0BG41-2AA0
6SL3000-0BG41-2AA0
6SL3000-0BG41-6AA0
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3