Technical Data; Basic Line Modules, 380 - Siemens SINAMICS S120 Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules
5.2 Basic Line Modules
Circuit breaker
The circuit breaker is used to connect the Basic Line Module to the line supply.
A 3WL1220 circuit breaker is recommended.
The circuit breaker is controlled via terminal -X9: 3, 4 of the Basic Line Module.
5.2.7

Technical data

5.2.7.1
Basic Line Modules, 380 ... 480 V 3 AC
Table 5- 13
Technical data for Basic Line Modules, 3 AC 380 V ... 480 V, Part 1
Article number
Rated output
- For I
(50 Hz, 400 V)
n_DC
- For I
(50 Hz, 400 V)
H_DC
- For I
(60 Hz, 460 V)
n_DC
- For I
(60 Hz, 460 V)
H_DC
DC-link current
- Rated current I
n_DC
- Base load current I
H_DC
- Maximum current I
max_DC
Input current
- Rated current I
n_E
- Maximum current I
max_E
- Maximum precharging current (max. 3 s)
Supply voltages
- Line voltage
- Line frequency
- Electronic power supply
- Fan supply voltage
- DC-link voltage
Current consumption
- Electronics current consumption (24 VDC)
- Fan power consumption (230 VAC)
Max. ambient temperature
- Without derating
- With derating
DC-link capacitance
- Basic Line Module
- Drive line-up, max.
Power loss, max.
1)
- at 50 Hz 400 V
- at 60 Hz 460 V
Cooling air requirement
Sound pressure level
L
(1 m) at 50/60 Hz
pA
Line/load connection
148
6SL3330–
1TE34–2AA3
kW
200
kW
160
HP
305
HP
245
A
420
A
328
A
630
A
365
A
547
A
internal
V
3 AC 380 -10% (-15% < 1 min) ... 3 AC 480 +10%
ACrms
Hz
V
DC
V
AC
V
1.35 x U
DC
A
1.1
A
1.1
° C
40
° C
55
µF
7200
µF
57600
kW
1.9
kW
1.9
m
/s
0.17
3
dB(A)
66 / 68
M10
1TE35–3AA3
1TE38–2AA3
250
400
200
315
385
615
305
485
530
820
413
640
795
1230
460
710
690
1065
internal
internal
47 ... 63 Hz
24 (20.4 ... 28.8)
230 (195.5 ... 264.5)
(partial load) / 1.32 x U
line
1.1
1.1
1.1
1.1
40
40
55
55
9600
14600
76800
116800
2.1
3.2
2.1
3.2
0.17
0.17
66 / 68
66 / 68
Flat connector for screw
M10
M10
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
1TE41–2AA3
560
450
860
690
1200
936
1800
1010
1515
internal
(full load)
line
1.1
4.5
40
55
23200
185600
4.6
4.6
0.36
71 / 73
M12

Advertisement

Table of Contents
loading