X530 Neutral Point Grounding - Siemens SINAMICS S120 Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.6.3.5

X530 neutral point grounding

Table 4- 25
Connector
The Voltage Sensing Module is supplied with inserted jumper. When delivered, the neutral
point is connected to the protective conductor via the connector jumper. Current can flow to
PE. This connection is removed by removing the connector jumper. The measurement is then
electrically isolated.
Figure 4-16
When the Active Interface Module is operated on an ungrounded line system (IT system), the
connection clip must be removed, see "Electrical connection (Page 94)".
Note
Replacing a VSM10 Voltage Sensing Module
When replacing a Voltage Sensing Module VSM10 by one with a different article number,
then inform yourself about the applicable boundary conditions.
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
Neutral point grounding X530
Terminal
Designation
1
Neutral point of the
voltage sensing
2
Ground potential
Internal circuit of the VSM10 Voltage Sensing Module
Line-side power components
4.6 Active Interface Modules
Technical specifications
Jumper inserted: Grounded measurement
Jumper not inserted: isolated measurement
87