Siemens SINAMICS S120 Manual page 363

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

NOTICE
Risk of damaging sine-wave filter by exceeding the maximum output frequency
The maximum permissible output frequency when sine-wave filters are used is 150 Hz. The
sine-wave filter can be damaged if the output frequency is exceeded.
• Operate the sine-wave filter with a maximum output frequency of 150 Hz.
NOTICE
Damage to the sine-wave filter if it is not activated during commissioning
The sine-wave filter may be damaged if it is not activated during commissioning.
• Activate the sine-wave filter during commissioning via parameter p0230 = 3.
NOTICE
Damage to the sine-wave filter if a motor is not connected
Sine-wave filters, which are operated without a motor being connected, can be damaged or
destroyed.
• Never operate a sine-wave filter connected to the Motor Module without a connected
Note
Cable lengths
Keep the connecting cables to the Motor Module as short as possible (max. 5 m).
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
motor.
Motor-side power components
8.1 Sine-wave filter
361