Cabinet design and EMC
9.4 Control cabinet installation for devices in the Chassis-2 format
9.4.2

Installing the devices in a Rittal VX25 control cabinet

9.4.2.1

Installing an Active Line Modules Chassis-2 or Motor Modules Chassis-2

Description
To install an Active Line Module Chassis-2 or Motor Module in a Rittal VX25 control cabinet,
you require a baseplate and a mounting plate for the rear panel of the control cabinet.
Models of the individual parts are also available in the "DT Configurator", see "DT Configurator
(https://www.siemens.com/dt-configurator)".
The following data applies for creating the base plate:
• All punch geometry dimensions, where a tolerance is not specified, must have a tolerance
of ±0.15; other dimensions - where the tolerance is not specified - must have a tolerance
according to ISO 2768 m-K.
• All bending radii shown in the drawings without dimensions must have radius R2.
• All radii shown in the drawings without dimensions must have radius R4.
• All chamfers shown in the drawings without dimensions must be implemented with
2 x 45°.
• Material for the sheet metal parts: EN10346-DX52D+Z140-M-B-CO-2.5.
• Punched edges should be deburred.
• You require 2 insert nuts, type KVT M10-H (number ① in the baseplate drawing).
The following data applies for creating the mounting plate for a 400 mm wide control
cabinet:
• All punch geometry dimensions, where a tolerance is not specified, must have a tolerance
of ±0.15; other dimensions - where the tolerance is not specified - must have a tolerance
according to ISO 2768 m-K.
• All bending radii shown in the drawings without dimensions must have radius R2.
• All radii shown in the drawings without dimensions must have radius R4.
• All chamfers shown in the drawings without dimensions must be implemented with
2 x 45°.
• Material for the sheet metal parts: EN10346-DX52D+Z140-M-B-CO-2.5.
• Punched edges should be deburred.
• You require 4 insert nuts, type KVT PEM-M10-H (number ① in the mounting plate
drawing).