6.2 Motor Modules Chassis-2
6.2.3.5

X9 terminal strip

Table 6- 27
Max. connectable cross-section: 2.5 mm
6.2.3.6

X41 EP terminal / temperature sensor connection

Table 6- 28
Max. connectable cross-section: 1.5 mm
At terminals 1 and 2, the terminal strip has a yellow marking, it is coded at terminal 4; please use the
corresponding connector from the accessory pack.
300
Terminal strip X9
Connector
Terminal
VL1
VL2
NC
HS1
HS2
P24V
M
Terminal strip X41
Connector
Terminal
1
2
3
4
5
6
Signal name
Technical specifications
Pre-charge contac-
240 V AC: 8 A max.
tor control
24 VDC: max. 1 A
isolated relay contact
NC
Reserved, do not use
Main contactor
240 V AC: 8 A max.
control
24 VDC: max. 1 A
isolated relay contact
P24V
External 24 V DC supply
Voltage: 24 V DC (20.4 ... 28.8 V)
M
Current consumption: max. 1.6 A
2
Function
Technical specifications
EP +24 V (enable
Supply voltage: 24 VDC (20.4 ... 28.8 V)
pulses)
Current consumption: 10 mA
The pulse inhibit function is only available
EP M1 (enable
when the "Safety Integrated Basic Functions
pulses)
via onboard terminals" is enabled in the soft-
ware.
+Temp (motor)
Temperature sensor connection: KTY84-1C130
/ PT100 / PT1000 / PTC
-Temp (motor)
NC
Reserved, do not use
NC
Reserved, do not use
2
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3