X9 terminal strip

Table 5- 47
Max. connectable cross-section: 2.5 mm
5.5.3.6

X41 EP terminal / temperature sensor connection

Table 5- 48
Max. connectable cross-section: 1.5 mm
At terminals 1 and 2, the terminal strip has a yellow marking, it is coded at terminal 4; please use the
corresponding connector from the accessory pack.
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
Terminal strip X9
Connector
Terminal
VL1
VL2
NC
HS1
HS2
P24V
M
Terminal strip X41
Connector
Terminal
1
2
3
4
5
6
Signal name
Technical specifications
Pre-charge contac-
240 V AC: 8 A max.
tor control
24 VDC: max. 1 A
isolated relay contact
NC
Reserved, do not use
Main contactor
240 V AC: 8 A max.
control
24 VDC: max. 1 A
isolated relay contact
P24V
External 24 V DC supply
Voltage: 24 V DC (20.4 ... 28.8 V)
M
Current consumption: max. 1.6 A
2
Function
Technical specifications
EP +24 V (enable
Supply voltage: 24 VDC (20.4 ... 28.8 V)
pulses)
Current consumption: 10 mA
EP M1 (enable
pulses)
+Temp
Temperature sensor connection: KTY84-
1C130/Pt1000/PTC
-Temp
NC
Reserved, do not use
NC
Reserved, do not use