Maintenance and Servicing

10.6 Forming the DC link capacitors

10.6
Forming the DC link capacitors
Description
If the Basic Line Module, Smart Line Module, Active Line Module, and Motor Module have not
been used for more than two years, the DC-link capacitors must be reformed. If this is not
carried out, the units could be damaged when the DC-link voltage is connected under load.
If the cabinet is commissioned within two years of its date of manufacture, the DC-link
capacitors do not need to be re-formed. The date of manufacture can be taken from the serial
number on the rating plate.
Note
Storage period
It is important that the storage period is calculated from the date of manufacture and not
from the date that the equipment was shipped.
Rating plate
Figure 10-38 Rating plate using an Active Line Module as example
538
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3