X609 Terminal Strip - Siemens SINAMICS S120 Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-side power components
4.6 Active Interface Modules
4.6.3.6

X609 terminal strip

Table 4- 26
X609 terminal strip
Connector
Terminal Designation
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Max. connectable cross-section: 2.5 mm
* Series connection NO contact of pre-charge contactor and bypass contactor (only for frame size FI, GI)
NOTICE
Device failure due to overtemperature caused by incorrect wiring of Active Interface
Modules with frame size HI and JI
During operation, Active Interface Modules of frame sizes HI and JI require a signal at
terminals X609:11 and X609:12 to control the fans. If this signal is not present during
operation, the fans do not rotate and the module is shut down on overtemperature.
• Connect the signals at terminals X609:11 and X609:12 to the Active Interface Modules
88
P24
P24
M
M
L
L
N
N
Pre-charge contactor–A1
Pre-charge contactor–A2
Bypass contactor–A1
Bypass contactor–A2
Contactor feedback 1 *
Contactor feedback 2 *
2
of frame sizes HI and JI to control the fans.
Technical specifications
External 24 V DC supply
Voltage: 24 VDC (20.4 ... 28.5 V)
Current consumption: Max. 0.25 A
Voltage: 230 VAC (195.5 ... 264.5 V)
Current consumption: Max. 10 A
Fan operating currents, see "Technical data"
Voltage: 230 VAC (195.5 ... 264.5 V)
Current consumption: Max. 4 A
Voltage: 230 VAC (195.5 ... 264.5 V)
Current consumption: Max. 6 A
Voltage: 230 VAC (195.5 ... 264.5 V)
Max. permissible current: 6 A
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
To Active Line Module, X9:5
To Active Line Module, X9:6
To Active Line Module, X9:3
To Active Line Module, X9:4
Air-cooled chassis power units

Advertisement

Table of Contents
loading

Table of Contents