Table 4- 14
Technical data of line reactors for Basic Line Modules, 3 AC 500 ... 690 V, Part 1
Article number
Suitable for
Basic Line Module
Rated power of the Basic
Line Module
Rated voltage
I
thmax
Power loss
Line/load connection
1U1, 1V1, 1W1, 1U2, 1V2,
1W2
PE connection
Degree of protection
Dimensions
Width
Height
Depth
Weight
Table 4- 15
Technical data of line reactors for Basic Line Modules, 3 AC 500 ... 690 V, Part 2
Article number
Suitable for
Basic Line Module
Rated power of the Basic
Line Module
Rated voltage
I
thmax
Power loss
Line/load connection
1U1, 1V1, 1W1, 1U2, 1V2,
1W2
PE connection
Degree of protection
Dimensions
Width
Height
Depth
Weight
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
6SL3000-
0CH32-7AA0
6SL3330-
1TG33-0AA3
kW
250
V
A
270
kW
0.277
M10 connecting
lugs
M6 screw
IP00
mm
270
mm
248
mm
200
kg
27.9
6SL3000-
0CH41-6AA0
6SL3330-
1TG41-8AA3
kW
1500
V
A
1600
kW
0.977
M12 connecting
lugs
M6 screw
IP00
mm
416
mm
435
mm
250
kg
134
4.4 Line reactors for Basic Line Modules
0CH34-8AA0
1TG34-3AA3
355
3 AC 500 -10% (-15% < 1 min) ... 3 AC 690 +10%
482
0.48
M12 connecting
lugs
M6 screw
IP00
350
321
232.5
55.6
3 AC 500 -10% (-15% < 1 min) ... 3 AC 690 +10%
Line-side power components
0CH36-0AA0
0CH41-2AA0
1TG36-8AA3
1TG41-1AA3
1TG41-4AA3
560
597
0.485
M12 connecting
M12 connecting
lugs
M6 screw
M6 screw
IP00
350
321
232.5
63.8
900
1100
1167
0.783
lugs
IP00
460
435
235
147
67