Minimum cable lengths for parallel connection and connection to a motor with a single-winding
system
Note
Minimum cable lengths
The minimum cable lengths specified in the tables below must be observed when two or
more Motor Modules Chassis-2 are connected in parallel and there is a connection to a motor
with a single-winding system. If the cable length required for the application cannot be
achieved, a motor reactor must be provided.
Table 6- 41
6SL3321-1TE36-6AA0
6SL3321-1TE37-4AA0
6SL3321-1TE38-1AA0
6SL3321-1TE38-8AA0
6SL3321-1TE41-0AA0
6SL3321-1TE41-1AA0
6SL3321-1TE41-2AA0
6SL3321-1TE41-3AA0
6SL3321-1TE41-5AA0
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
Motor Modules Chassis-2, 510 ... 720 V DC (line voltage 3 AC 380 ... 480 V)
Article number
Type rating
Output current
[kW]
315
655
355
740
400
810
450
910
500
975
560
1075
630
1200
710
1325
800
1495
6.2 Motor Modules Chassis-2
Minimum cable length
[A]
Motor Modules
[m]
13
12
10
9
8
8
8
8
8