NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Ensure that the rubber ring is not disconnected. If the rubber ring is disconnected
or damaged, seal the gaps around the pipes with mastic cement or thermal
insulation foam.
Step 4 Route the straight-through pipe through the pipe hole at the bottom of the
cabinet and connect the pipe to the PPR pipe using a hot melt gun, as shown by
(3) in
Step 5 Connect the drainpipe to the external drainage system.
The drainpipes must have gradients (> 1:100), and stagnant water is not allowed.
----End
Top Pipe Routing
When routing pipes from the top, do not route the pipes over servers or other
devices to protect them from being affected by pipe leaks.
Step 1 Remove the drainpipe plug, as shown in
Figure 4-71 Top pipe routing
Step 2 Route the drainpipe from the top by referring to
routing.
----End
4.8.8 (Optional) Installing the Humidifier Water Inlet Pipe
Issue 08 (2021-09-17)
NO TICE
Figure
4-70.
NO TE
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Figure
4-71.
Step 2–Step 5
4 Installation
of the bottom pipe
95