NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Figure 4-55 Removing the low temperature component

4.6.3 Securing a Low temperature Component

Place the low temperature component on a concrete platform, and align the
mounting holes with the holes in the concrete platform. Secure the low
temperature component to the concrete platform using four M12 x 60 stainless
steel expansion bolts to a torque of 45 N·m, as shown in
Figure 4-56 Securing a low temperature component

4.7 Installing the Water Cooling Module

4.7.1 Checking the Nitrogen Pressure

Check whether any of the two needle valve bonnets is missing by turns.
Issue 08 (2021-09-17)
If they do not exist, contact Huawei technical support.
Copyright © Huawei Technologies Co., Ltd.
4 Installation
Figure
4-56.
83