Huawei NetCol5000-A050 User Manual page 277

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Figure 11-22 Installing the compressor bracket
● During welding, use a silver copper welding rod containing 5% silver. Check
that the welding joints are in good condition, without poor soldering.
● To avoid burning the internal components, other pipes, thermal insulation
foam, power cables, and labels, take protective measures, such as spreading
wet cloth, around the welding position.
● Do not use face-down bonding when welding.
● After the installation, check that the input power cables of the compressor are
in the same phase sequence as the wiring terminals.
Step 9 Secure the compressor bracket to the cabinet interior using a 13# socket wrench,
as shown by (1) in
Figure 11-23 Installing the compressor
Issue 08 (2021-09-17)
NO TICE
Figure
Copyright © Huawei Technologies Co., Ltd.
11-23.
11 Parts Replacement
267