Huawei NetCol5000-A050 User Manual page 236

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Alarm
ID
A282-0
4
A282-0
8
A282-1
0
A282-4
0
A282-0
1
A282-0
2
A282-0
4
Issue 08 (2021-09-17)
Alarm Name
Alar
m
Seve
rity
Power phase
CRITI
sequence
CAL
abnormal
Power phase
CRITI
sequence
CAL
abnormal
Power phase
CRITI
sequence
CAL
abnormal
Power phase
CRITI
sequence
CAL
abnormal
Power phase
MAJ
sequence
OR
abnormal
Backup power
MAJ
phase
OR
sequence
abnormal
Backup power
MAJ
phase
OR
sequence
abnormal
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
1. The power grid
is unstable.
2. The phase A
input cable is
faulty.
1. The power grid
is unstable.
2. The phase B
input cable is
faulty.
1. The power grid
is unstable.
2. The phase C
input cable is
faulty.
1. The power grid
is unstable.
2. The phase B
input cable is
faulty.
1. The power grid
is unstable.
2. The SPD and
voltage detection
board may be
faulty if it is
configured.
1. The phase
sequence of the
power supply is
incorrect.
2. The SPD and
voltage detection
board is faulty.
1. The power grid
is unstable.
2. The phase A
input cable is
faulty.
9 Alarm Reference
Solution
1. Check the power
grid.
2. Rectify the fault of
the phase A input
cable.
1. Check the power
grid.
2. Rectify the fault of
the phase B input cable.
1. Check the power
grid.
2. Rectify the fault of
the phase C input cable.
1. Check the power
grid.
2. Rectify the fault of
the phase B input cable.
1. Check the power
grid.
2. Maintain or replace
the SPD and voltage
detection board.
1. Rectify the phase
sequence of the power
supply.
2. Maintain or replace
the SPD and voltage
detection board.
1. Check the power
grid.
2. Rectify the fault of
the phase A input
cable.
226

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents