Huawei NetCol5000-A050 User Manual page 217

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Alarm
ID
A134-0
1
A143-0
1
Issue 08 (2021-09-17)
Alarm Name
Alar
m
Seve
rity
Compressor
MAJ
suction
OR
temperature
sensor fault
Outdoor unit
MAJ
communicatio
OR
n failed
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
1. The cables to
the suction
temperature
sensor are loose or
damaged.
2. The suction
temperature
sensor is faulty.
1. The
communications
cable between the
indoor and
outdoor units is
not properly
connected.
2. The outdoor fan
drive is faulty.
3. The outdoor
unit is not
powered on.
4. The
communications
port of the main
control board is
faulty.
9 Alarm Reference
Solution
1. Check cables to the
suction temperature
sensor.
2. Maintain or replace
the suction temperature
sensor.
1. Check the
communications cable
between the indoor and
outdoor units.
2. Maintain or replace
the outdoor fan drive.
3. Power on the
outdoor unit.
4. Maintain or replace
the main control board.
207