Huawei NetCol5000-A050 User Manual page 214

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Alarm
ID
A089-0
1
A093-0
1
Issue 08 (2021-09-17)
Alarm Name
Alar
m
Seve
rity
Compressor
MAJ
drive speed
OR
limit alarm
High humidity
WAR
alarm
NIN
G
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
1. The compressor
lacks oil.
2. The refrigerant
leaks.
1. The thermal
load power is low.
2. The ambient
humidity exceeds
the upper
threshold.
3. The
temperature and
humidity sensor is
not installed in a
proper position.
4. The high
humidity alarm
threshold is
inappropriate.
5. The value
detected by the
temperature and
humidity sensor is
different from the
actual value.
9 Alarm Reference
Solution
1. Fill oil to the
compressor.
2. Identify and repair
the leaking point, and
refill refrigerant after
maintenance.
1. Contact Huawei
technical support.
2. Measure the ambient
humidity.
3. Adjust the position of
the temperature and
humidity sensor.
4. Adjust the high
humidity alarm
threshold.
5. Calibrate or replace
the temperature and
humidity sensors.
204