Optional) Setting Teamwork Control Parameters - Huawei NetCol5000-A050 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Procedure
Step 1 On the home screen, choose Settings > System Settings > Indoor Fan, and set
Air-side difference pressure sensor type to 0–50 Pa.
Step 2 Set Indoor fan control type to Pressure diff ctrl.
Step 3 Change the other parameters based on the following instructions.
Table 6-6 Parameter description
Parameter
Indoor fan control type
Indoor fan pressure
difference setpoint
Air-side difference
pressure sensor type
Min indoor fan speed
Max indoor fan speed
----End

6.5.3 (Optional) Setting Teamwork Control Parameters

Prerequisites
The teamwork group number and addresses for the smart cooling products have
been set as follows:
Issue 08 (2021-09-17)
Teamwork group No.: Group the smart cooling products in same aisle or
adjacent areas as one, that is, assign one teamwork group number for them.
At most four teamwork groups can be assigned (1–4).
Copyright © Huawei Technologies Co., Ltd.
Description
Specifies the control type
for the indoor fan.
Specifies the differential
pressure control
threshold.
Specifies the measuring
range for the air-side
differential pressure
sensor.
Specifies the minimum
speed for the indoor fan.
Specifies the maximum
speed for the indoor fan.
6 Power-On Commissioning
Setting Rule
Normally, retain R/S air
temp diff rate ctrl. If
the differential pressure
sensors are installed,
change to Pressure diff
ctrl.
The default value is 10
Pa. When there are
partial hot spots indoors,
you are advised to raise
the value to ensure that
the air volume of the
indoor fans is between
60%–70%.
There is no default value.
Set it to 0–50 Pa.
The default value is 30%.
You are advised not to
change the value.
The default value is
100%.
142