Huawei NetCol5000-A050 User Manual page 155

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Paramete
r
Number
of running
systems in
this group
Rotation
function
Rotation
period
Rotation
time
Forced
rotation
Issue 08 (2021-09-17)
Description
Specifies the number of
running units in this group.
The value is an integer
ranging from 1 to the value
of Number of systems in
this group.
Indicates whether to allow
the smart cooling products
to work as the standby
device in turn, maximizing
their service life.
Rotation days (1–30).
24 hours in a day (0–23).
Indicates whether to enable
forced rotation regardless
of the specified rotation
time. After a forced
rotation, the rotation period
starts again.
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Setting Rule
The master unit
assigns running units
in ascending order of
the addresses. The
address should be in
the range of 1–32. The
remaining units are
automatically
classified as standby
devices.
It is recommended
that the function be
enabled when the
load is even.
7 by default
0 by default
This item is set to No
by default. If forced
rotation is required,
the function is set to
Yes.
Default
Value
2
Disable
7 day (s)
0
No
145