Figure 4-25 Pagoda connector (unit: mm)

4.2.2.6 Pipe Support

Figure 4-26
appearance of the supports will be different based on onsite situations.
Figure 4-26 Pipe supports (unit: mm)

4.2.2.7 Cables

Table 4-15 Recommended cables
Item
Active/standby power
cable for the indoor unit
Issue 08 (2021-09-17)
shows supports for refrigerant pipes and water pipes. The actual
NO TE
● The height of the U-shaped pipe clamp is 5 mm less than the pipe diameter (including
the thermal insulation foam). Pipe supports are subject to engineering procurement.
● It is recommended that pipe supports and pipe clamps be made of 304 stainless steel.
● Install a support every 1500 mm for the straight sections of pipes, and 500 mm away
from each bending point in turning sections.
Copyright © Huawei Technologies Co., Ltd.
Recommended circuit
breaker
4 Installation
NetCol5000-A050
63 A/3P (feature C)
57