Huawei NetCol5000-A050 User Manual page 240

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Alarm
ID
A28C-0
8
Issue 08 (2021-09-17)
Alarm Name
Alar
m
Seve
rity
Compressor
CRITI
high discharge
CAL
pressure alarm
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
1. The input power
of the outdoor
unit has an open
phase, incorrect
phase sequence,
or is unavailable.
2. Cables to the
indoor or outdoor
fan are not
properly
connected.
3. The condenser
fins are dirty or
blocked.
4. The outdoor fan
or its drive is
faulty.
5. The high
pressure switch is
faulty.
6. The refrigerant
is overfilled.
7. The exhaust fan
is faulty.
9 Alarm Reference
Solution
1. Check the input
power of the outdoor
unit.
2. Check the cables to
the indoor and outdoor
fans.
3. Clean the condenser
fins.
4. Maintain or replace
the outdoor fan or its
drive.
5. Maintain or replace
the high pressure
switch.
6. Decrease certain
amount of refrigerant.
7. Maintain or replace
the exhaust fan.
230

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents