Startup - Huawei NetCol5000-A050 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual

6.6 Startup

Context
Tap the Start or Shutdown buttons on the home screen to start or shut down the
smart cooling product.
Procedure
Step 1 Tap Start on the home screen of the controller.
Issue 08 (2021-09-17)
If the device is powered on again after a power failure, the device
automatically restores to the original start/shutdown state before the power
failure.
Hardware ports are reserved on the controller to control the status of the
remote dry contacts or remote startup and shutdown signal. The status of the
remote dry contacts and remote start/shutdown signal is started by default.
Starting a unit over the screen or NMS is valid only when the status of remote
dry contacts or remote start/shutdown signal is Start.
If the screen shown in
startup, perform
Step 2
Figure 6-29 Initial startup
Figure 6-30 Password screen
If the screen shown in
tap Yes to start the smart cooling product.
Copyright © Huawei Technologies Co., Ltd.
Figure 6-29
is displayed, tap Yes. Indicating initial
for initial startup verification.
Figure 6-31
is displayed, indicating not initial startup,
6 Power-On Commissioning