NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Context
The parameters in this section are for reference only. Set practical parameter
values as required.
Procedure
Step 1 On the home screen, tap
Settings screen, as shown in
Figure 6-11 Teamwork settings
Step 2 Set teamwork control parameters.
All teamwork control parameters can be set on the master smart cooling product.
Only Teamwork group No., System address, Enable teamwork CAN resistor,
Teamwork function and Networking mode can be set on slave smart cooling
products. Other parameters of the slave units will be modified by the master unit
synchronously.
Table 6-7 Teamwork settings
Paramete
r
Teamwork
group No.
System
address
Issue 08 (2021-09-17)
System address: The address (configurable range: 1-32) of each smart cooling
product in the same group must be unique. The smart cooling product with
the smallest unit address is the master unit, which collects, processes, and
delivers group data.
Table 6-7
describes how to set the parameters.
Description
The number of the
teamwork group. This
parameter should be the
same for all units in the
same teamwork group.
The addresses of units in
the same teamwork group
cannot be the same.
Copyright © Huawei Technologies Co., Ltd.
> Teamwork Settings to enter the Teamwork
Figure
6-11.
Setting Rule
Set the assigned
teamwork control
number.
Set the planned unit
address.
6 Power-On Commissioning
Default
Value
1
NA
143