Optional) Setting Differential Pressure Control Parameters - Huawei NetCol5000-A050 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Parameter
Temperatur
e control
mode
Temperatur
e setpoint
Humidity
setpoint
----End
6.5.2 (Optional) Setting Differential Pressure Control
Parameters
Prerequisites
If the differential pressure sensors are installed, perform the following operations
accordingly. If the differential pressure sensors are not installed, skip this part.
Issue 08 (2021-09-17)
Description
This parameter controls the
temperature inside the room or
aisles based on the Average
value, Max value, or Min
value of the temperatures
collected by each sensor.
After the Temperature and
humidity control type and the
temperature value under this
type are set, the device
conducts cooling or heating
based on the settings.
After the Temperature and
humidity control type and the
humidity value under this type
are set, the device conducts
humidifying or dehumidifying
based on the settings.
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Configuration Principle
● Average value: Select
Average value if the
temperature is to be
controlled based on the
averaged data value
collected by the collector.
● Max value: Select Max
value if the temperature is
to be controlled based on
the maximum data value
collected by the collector.
● Min value: Select Min value
if the temperature is to be
controlled based on the
minimum data value
collected by the collector.
You are advised to retain the
default setting Average
value.
Set this parameter as required.
● Return air temperature: 26–
35°C recommended
● Supply air temperature: 18–
24°C recommended
● Cold aisle temperature: 18–
24°C recommended
● Hot aisle temperature: 26–
35°C recommended
Set this parameter as required.
40%–60% RH recommended
141