Huawei NetCol5000-A050 User Manual page 133

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Procedure
Step 1 Check whether a low temperature component is installed on the outdoor side.
Figure 6-2 Vacuumizing the system with a low temperature component
(1) Vacuum pump
(4) Low-pressure needle valve (5) Exhaust pipe needle valve
Issue 08 (2021-09-17)
If no low temperature component is installed on the outdoor side, connect the
pressure gauge and vacuum pump at the low-pressure and exhaust pipe
needle valves to vacuumize the system simultaneously, as shown in
6-1.
Figure 6-1 Vacuumizing the system without a low temperature component
(1) Vacuum pump
(3) Low-pressure needle valve
If a low-temperature component is installed on the outdoor side, connect the
pressure gauge and vacuum pump at the low-pressure, exhaust pipe, and
liquid pipe needle valves to vacuumize the system simultaneously, as shown
in
Figure
6-2.
Copyright © Huawei Technologies Co., Ltd.
(2) Pressure gauge
(4) Exhaust pipe needle valve
(2) Pressure gauge 1
6 Power-On Commissioning
Figure
(3) Pressure gauge 2
(6) Liquid pipe needle valve
123