• For the following parameters, set the FR-CC2 parameters as required.
Pr.57 Restart coasting time
Pr.65, Pr.67, and Pr.68 (Retry selection)
Pr.256 Inrush current limit circuit life display
Pr.258 and Pr.259 (Life of main circuit capacitor)
Pr.872 Input phase loss protection selection
 To convert from FR-F700(P) inverters to FR-F800(-E) inverters
• Set the following parameters as required in the "Parameter list" window because they are not converted.
Pr.69 Retry count display erase
Pr.170 Watt-hour meter clear
Pr.171 Operation hour meter clear
Pr.172 to Pr.174 (User group selection)
Pr.259 Main circuit capacitor life measuring
Pr.498 PLC function flash memory clear
Pr.501 (Communication option parameter)
Pr.503, Pr.686, and Pr.688 (Maintenance timer)
Pr.898 Power saving cumulative monitor clear
Pr.991 PU contrast adjustment
Pr.1006 to Pr.1008 (Clock function)
Pr.1020 Trace operation selection
Pr.1219 PID gain tuning start/status
• When parameter settings are converted from FR-F700(P) (FM type) inverters to FR-F800 (CA type) inverters or from FR-
F700(P) (CA type) inverters to FR-F800 (FM type) inverters, set the following parameters as required in the "Parameter
list" window because they are not converted.
Pr.54 FM/CA terminal function selection
Pr.869 Current output filter
C8 (Pr.930) to C11 (Pr.931) (Terminal CA calibration parameters)
• It is recommended to adjust the setting of the following parameters again after conversion according to the mechanical
system because they are used for adjustment.
Pr.0 Torque boost
Pr.12 DC injection brake operation voltage
C2 (Pr.902) to C7 (Pr.905) (Frequency setting input calibration parameters)
• Since the communication-related parameters (Pr.117 to Pr.124, Pr.331 to Pr.337, Pr.341, Pr.547, and Pr.548) are also
converted, communication may be disabled depending on the setting after the setting is written to parameters. For
example, when Pr.122/Pr.336 RS-485 communication check time interval = "0 (initial value)", a communication error
(E.PUE, E.SER) occurs immediately after the operation mode with the command source is selected.
• Set the following parameter as required in the "Parameter list" window because they are not converted depending on the
setting of the source inverter.
Pr.52 Operation panel main monitor selection
Pr.54 FM/CA terminal function selection
Pr.158 AM terminal function selection
Pr.190 to Pr.196 (I/O terminal function assignment)
Pr.306 Analog output signal selection
Pr.310 Analog meter voltage output selection
Pr.313 to Pr.322 (Output selection)
Pr.774 to Pr.776 Operation panel monitor selection
*1
*1
*1
1
2
3
4
5
6
7
8
9
10
127