Mitsubishi Electric MELSOFT FR Configurator2 Instruction Manual page 42

Table of Contents

Advertisement

Pr.
Name
1425
Ethernet communication station
N651
number
1442
IP filter address 1 (Ethernet)
N660
1443
IP filter address 2 (Ethernet)
N661
1444
IP filter address 3 (Ethernet)
N662
1445
IP filter address 4 (Ethernet)
N663
1446
IP filter address 2 range specification
N664
(Ethernet)
1447
IP filter address 3 range specification
N665
(Ethernet)
1448
IP filter address 4 range specification
N666
(Ethernet)
1449
Ethernet command source selection IP
N670
address 1
1450
Ethernet command source selection IP
N671
address 2
1451
Ethernet command source selection IP
N672
address 3
1452
Ethernet command source selection IP
N673
address 4
1453
Ethernet command source selection IP
N674
address 3 range specification
1454
Ethernet command source selection IP
N675
address 4 range specification
NOTE
• Always reset the inverter after making the setting of the parameters. After you have changed the communication-related
parameters, communication cannot be established until the inverter reset.
• Set "5001" in any parameter from Pr.1427 to Pr.1429 to enable automatic recognition or switching to online connection during
communication through "CPU module" or "Ethernet module". When the initial settings are used, there is no need to change.
(Refer to
page
72.)
• FR-A800-E-R2R
Pr.
Name
550
NET mode operation command source
D012
selection
551
PU mode operation command source
D013
selection
Initial
Setting range
value
1
120
Set the station number from 1 to 120.
0
0 to 255
0
0 to 255
0
0 to 255
Set the range of connectable IP addresses for the
network devices.
0
0 to 255
(When Pr.1442 to Pr.1445 = "0 (initial value)", the
function is invalid.)
9999
0 to 255, 9999
9999
0 to 255, 9999
9999
0 to 255, 9999
Set the range of IP addresses to limit the network
0
0 to 255
devices that can be used as a command source during
Ethernet communication (with MODBUS/TCP
0
0 to 255
protocol).
When Pr.1449 to Pr.1452 = "0 (initial value)", no IP
0
0 to 255
address is specified for command source selection via
Ethernet. In this case, operation commands cannot be
sent via Ethernet with MODBUS/TCP protocol.
0
0 to 255
When four or more clients attempt a connection to the
inverter during MODBUS/TCP protocol
9999
0 to 255, 9999
communication, the connection attempted from
outside of the IP address range set for Ethernet
9999
0 to 255, 9999
command source selection may be forced to be
closed.
Initial
Setting range
value
The communication option is the command interface
0
enabled in the NET operation mode.
The Ethernet connector is the command interface
5
enabled in the NET operation mode.
9999
Communication option is recognized automatically.
Basically, the RS-485 terminals are the command
9999
interface. When the communication option is installed,
the communication option is the command interface.
The PU connector is the command interface enabled
2
in the PU operation mode.
The USB connector is the command interface in the
3
PU operation mode.
The Ethernet connector is the command interface in
9999
5
the PU operation mode.
USB automatic recognition
Basically, the operation panel (PU connector) is the
9999
command interface. When the USB connector is used,
it is the command interface.
Description
Description
1. OUTLINE
1.4 Connection and parameter setting
1
2
3
4
5
6
7
8
9
10
41