Dedicated instruction
The dedicated instructions used for an interrupt from a programmable controller CPU are shown below.
Instruction
Execution
condition
DP.GINT
D.GINT
: Available, : Partly available
Setting
Available device
*1
data
Internal device
(System, user)
Bit
Word
(n1)
(n2)
*2
*3
(D1)
*2
*3
(D2)
*1 Can be index-modified. (Constant is excluded.)
*2 Can be omitted only when both of (D1) and (D2) are omitted.
*3 Local devices cannot be used.
■Setting data
Setting data
Setting content
(n1)
The start I/O number of the target CPU divided by 16
The values to be specified actually are as follows:
CPU No.1: 3E0H, CPU No.2: 3E1H, CPU No.3: 3E2H, CPU No.4: 3E3H
(n2)
Interrupt pointer number (0 to 15)
*1
(D1)
(D1+0): Device that is turned ON for one scan upon completion of the instruction processing
(D1+1): Device that is turned ON for one scan upon abnormal completion of the instruction processing
(For abnormal completion, D1+0 also turns ON.)
*1
(D2)
Device where the completion status is stored.
*1 Can be omitted only when both of (D1) and (D2) are omitted.
Command
Command
Command
Command
File register
Link direct
device
J\
Bit
Word
Bit
Word
*3
*3
DP.GINT
DP.GINT
(n1)
(n2)
D.GINT
D.GINT
(n1)
(n2)
Module access
Index
device
register
J\
Z
Bit
Word
12 BUS ACCESS FUNCTION
12.3 Interrupt Notification Reception
(n1)
(n2)
(D1)
(D2)
(n1)
(n2)
(D1)
(D2)
Constant
Others
Dec K,
Float,
Hex H
string
Setting side
Data type
User
BIN16 bits
User
BIN16 bits
System
Bit
System
Word