Diagnostics information
The special registers for diagnostics information are as follows.
No.
Name
Description
SD0
Latest self-
Latest self-
diagnostics error
diagnostics error
code
code
SD1
Self-diagnostics
Self-diagnostics
error occurrence
error occurrence
time
time
SD2
SD3
SD4
SD5
SD6
SD7
SD10
Self-diagnostics
Self-diagnostics
error code
error code 1
SD11
Self-diagnostics
error code 2
SD12
Self-diagnostics
error code 3
SD13
Self-diagnostics
error code 4
SD14
Self-diagnostics
error code 5
SD15
Self-diagnostics
error code 6
SD16
Self-diagnostics
error code 7
SD17
Self-diagnostics
error code 8
SD18
Self-diagnostics
error code 9
SD19
Self-diagnostics
error code 10
SD20
Self-diagnostics
error code 11
SD21
Self-diagnostics
error code 12
SD22
Self-diagnostics
error code 13
SD23
Self-diagnostics
error code 14
SD24
Self-diagnostics
error code 15
SD25
Self-diagnostics
error code 16
SD53
AC/DC DOWN
Number of times for
AC/DC DOWN
detection
SD60
Number of module
Number of module
with blown fuse
with blown fuse
SD61
I/O module verify
I/O module verify
error module
error module
number
number
Details
Error codes are stored in hexadecimal when an error is detected with the
diagnostics.
• The same information as the latest information displayed on the error
history is displayed.
The year (four digits) when SD0 data was updated is stored as a BIN
code.
The month when SD0 data was updated is stored as a BIN code.
The date when SD0 data was updated is stored as a BIN code.
The hour when SD0 data was updated is stored as a BIN code.
The minute when SD0 data was updated is stored as a BIN code.
The second when SD0 data was updated is stored as a BIN code.
The day of the week when SD0 data was updated is stored as a BIN
code. (0: Sun, 1: Mon, 2: Tue, 3: Wed, 4: Thu, 5: Fri, 6: Sat)
Up to 16 types of error codes are stored to SD10 and higher when the
diagnostics detects errors. (The same error code as the one already
stored in SD10 and later is not stored.) The 17th and succeeding error
codes are not stored, in addition to the case that 16 types of error codes
have already been stored to SD10 to SD25.
A value is incremented by one each time when input voltage drops to 85%
(AC power)/65% (DC power) or less of the rated value while this product
is in operation, and stored as a BIN code.
A counting cycle from 0  65535  0 is repeated.
The lowest I/O number of module in which a fuse blew is stored.
The lowest I/O number of the module in which an I/O module verification
error has been detected is stored.
Set by (when to set)
S (error occurrence)
S (error occurrence)
S (error occurrence)
S (error occurrence)
S (error occurrence)
S (error occurrence)