Error
Error name
code
2441H
Module major error
2442H
Module major error
2443H
Module major error
2450H
Module major error
2460H
Another CPU module
major error
2461H
Another CPU module
major error
2462H
Another CPU module
major error
2463H
Another CPU module
major error
33 ERROR CODE LIST
238
33.1 Error Codes for Self-diagnostics
Error details and cause
• An error has been detected in the
intelligent function module when the
function was executed.
• An error was detected in the
intelligent function module when a
function was executed.
• An error was detected in the I/O
module or intelligent function module.
• A major error has been notified from
the intelligent function module
connected.
• The I/O module or intelligent function
module is not mounted properly or
was removed during operation.
• An error has been detected in another
CPU module during the initial
processing of the bus control.
• An error has been detected in another
CPU module when the function was
executed.
• An error has been detected in another
CPU module when the function was
executed.
• An error has been detected in another
CPU module.
Corrective action
• Take measures to reduce noise.
• Reset the bus. If the same error code
is displayed again, the possible cause
is a hardware failure of the error
module. Please contact your local
Mitsubishi Electric sales office or
representative.
• Take measures to reduce noise.
• Reset the bus. If the same error code
is displayed again, the possible cause
is a hardware failure of the error
module. Please contact your local
Mitsubishi Electric sales office or
representative.
• Take measures to reduce noise.
• Reset the bus. If the same error code
is displayed again, the possible cause
is a hardware failure of the error
module. Please contact your local
Mitsubishi Electric sales office or
representative.
• Take measures to reduce noise.
• Check the connection status of the
extension cable.
• Check the detailed information
(system configuration information) of
the error by executing module
diagnostics using CW Configurator
and check the module corresponding
to the displayed slot number.
• Reset the bus. If the same error code
is displayed again, the possible cause
is a hardware failure of the error
module. Please contact your local
Mitsubishi Electric sales office or
representative.
• Take measures to reduce noise.
• Reset the bus. If the same error code
is displayed again, the possible cause
is a hardware failure of the host CPU
module or another CPU module
where the error has been detected.
Please contact your local Mitsubishi
Electric sales office or representative.
• Take measures to reduce noise.
• Reset the bus. If the same error code
is displayed again, the possible cause
is a hardware failure of the host CPU
module or another CPU module
where the error has been detected.
Please contact your local Mitsubishi
Electric sales office or representative.
• Take measures to reduce noise.
• Reset the bus. If the same error code
is displayed again, the possible cause
is a hardware failure of the host CPU
module or another CPU module
where the error has been detected.
Please contact your local Mitsubishi
Electric sales office or representative.
• Take measures to reduce noise.
• Reset the bus. If the same error code
is displayed again, the possible cause
is a hardware failure of the host CPU
module or another CPU module
where the error has been detected.
Please contact your local Mitsubishi
Electric sales office or representative.
Stop/
Diagnostic
continue
timing
Stop/continue
At instruction
execution
Stop/continue
At module
access
Stop
At module
access
Stop/continue
Always
Stop
Power-on,
hardware
reset, bus
reset
Stop/continue
At instruction
execution
Stop/continue
At fixed cycle
processing
execution
Stop
Power-on,
hardware
reset, bus
reset