Mitsubishi Electric MELSEC iQ-R Series User Manual page 283

Programmable controller
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

No.
Name
Description
SD113
Detailed information
Detailed information
to
2
2
SD143
Details
■(5) System configuration information
b15
With or without specification
SD113
I/O No.
SD114
SD115
Base unit No.
Power supply module
CPU No.
SD116
Network No.
SD117
Station No.
SD118
The following information is stored in SD113.
• b0: I/O No.
• b1: Slot No.
• b2: Base unit No.
• b3: Power supply module No.
• b4: CPU No.
• b5: Network No.
• b6: Station No.
The slot No. (0 to 11) is stored in SD115 (b0 to b7).
The base No. is stored in SD115 (b8 to b15).
• 0: Main base unit
• 1 to 7: Extension base unit, level 1 to 7
• 8: Extension base unit, level 8 (when the number of base is exceeded)
The power No. (1 to 2) is stored in SD116 (b0 to b7).
The CPU No. (1 to 4) is stored in SD116 (b8 to b15).
The network No. (0 to 120) is stored in SD117. (0 for a master station)
Set by (when to set)
S (error occurrence)
b0
Slot No.
No.
Appendix 5 Special Register List
A
APPX
281

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r melsecwincpu

Table of Contents