Checking and disabling settings from list window
From the "Check/Disable Register Device Test with Execution Condition" window, the following operations can be performed:
checking the registered settings, disabling selected settings, registering/disabling settings in batch, and reading/writing
registered settings from/to a file.
[Debug]  [Device Test with Execution Condition]  [Check/Disable Register]
Window
Displayed items
Item
PLC Operation
[Update Status] button
for Device Test
Condition
[Disable Selected
Conditions] buttons
[Batch Register] button
[Batch Disable] button
File Operation
[Read File] button
[Write File] button
The registered settings of the device test with execution conditions can be collectively disabled by the
following operation in the engineering tool: [Debug]  [Device Test with Execution Condition]  [Batch
Disable]
■Disabling device test with execution conditions
In addition to the operations from the engineering tool, the following operations can be used to disable the device test with
execution conditions.
• Powering off and on
• Resetting the CPU module
• Writing a program to the CPU built-in memory by writing data to the programmable controller while the CPU module is in
*1*4
the STOP state
19 TEST FUNCTION
246
19.2 Device Test with Execution Conditions
Description
Click this button to read the registered settings of the device test with execution conditions in the CPU module.
No data is read when this operation is performed with no settings registered.
Click this button to disable the selected registration of the device test with execution conditions that has been
read from the CPU module by using the [Update Status] button.
All the existing registered settings of the device test with execution conditions in the CPU module are disabled by
clicking this button, and the settings that have been read by using the [Update Status] button or [Read File]
button are registered to the CPU module.
Click this button to collectively disable the registered settings of the device test with execution conditions in the
CPU module.
Click this button to read the registered settings of the device test with execution conditions, which have been
saved by using the [Write File] button, and list them on the window.
Click this button to save the registered settings of the device test with execution conditions listed on the window
into a file in the personal computer.