Error
Error name
Error details and cause
code
2803H
I/O number or
• The I/O number of the module that
network number
cannot be specified in the instruction
specification
was specified.
error
2804H
• The specified network number is out
of range (other than 1 to 239).
2805H
• The network number that does not
exist was specified.
2806H
I/O number or
• An I/O module or intelligent function
network number
module controlled by another CPU
specification
module was specified.
error
2807H
I/O number or
• The module cannot be identified in the
network number
instruction that requires a
specification
specification of the I/O module or
error
intelligent function module.
(There is a mistake in the string
specifying the module.)
2810H
I/O number or
• The I/O module or intelligent function
network number
module specified in the instruction
specification
cannot execute the instruction.
error
2820H
Device, label, or
• The device or label area used in the
buffer memory
instruction exceeded the specified
specification
range.
error
• The file register file is not set or was
accessed without setting it in the CPU
parameters (file setting).
2821H
Device, label, or
• The device or label areas used in the
buffer memory
instruction to store data are
specification
overlapping.
error
2822H
• The device or label that cannot be
used in the instruction was specified.
2823H
• The buffer memory area of the
module specified in the instruction
exceeded the specified range.
• The module specified in the
instruction does not have buffer
memory.
2824H
• The access prohibited area in the
buffer memory was accessed.
Stop/
Action
continue
Stop/
• Check the detailed information
continue
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
Stop/
• Check the detailed information
continue
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
• Delete the link direct device that
specifies a network module
controlled by another CPU module
from the program.
• Specify a network module
controlled by host CPU module by
using the link direct device.
Stop/
• Check the detailed information
continue
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
Stop/
• The possible cause is a hardware
continue
failure of the I/O module or
intelligent function module
specified in the instruction. Please
consult your local Mitsubishi
representative.
Stop/
• Check the detailed information
continue
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
• Set the file register file in
parameter, and access the file.
Stop/
• Check the detailed information
continue
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
Detailed
Diagnostic
information
timing
Error location
At instruction
information,
execution
system
configuration
information
Error location
At instruction
information,
execution
system
configuration
information
Error location
At instruction
information
execution
Error location
At instruction
information,
execution
system
configuration
information
Error location
At instruction
information,
execution, at
process
END
control
instruction
instruction
execution
processing
information
Error location
At instruction
information,
execution
process
control
instruction
processing
information
Error location
information
36 ERROR CODES
577
36.4 List of Error Codes
36

Advertisement

Table of Contents
loading

Table of Contents