Mitsubishi Electric MELSEC iQ-R Series User Manual page 590

Process cpu module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error name
code
3400H
Operation error
3401H
3402H
3403H
3404H
3405H
3406H
3420H
3421H
Operation error
3422H
Operation error
3423H
Operation error
3424H
Operation error
36 ERROR CODES
588
36.4 List of Error Codes
Error details and cause
• Division where the divisor is zero was
performed.
• Data that cannot be converted by
using the data conversion instruction
was input.
• The operation was performed with the
invalid data (-0, denormalized
number, NaN (not a number), or ).
• An overflow has occurred during the
operation.
• A string that is not supported in the
instruction was specified.
• The input data was out of range.
• The operation result is out of the
output range. (The operation result of
the instruction that concatenate
character strings exceeded the
allowable number of characters.)
• The link direct device, module access
device, or CPU buffer memory access
device is specified for both (s) and (d)
used in the BMOV instruction.
• When writing data to the data memory
by using the SP.DEVST instruction,
the number of writes per day
exceeded the number set in SD771.
• The value set in SD771 is out of
range.
• The structure of the PID control
instruction is incorrect.
• The size of data to be sent/received
by the socket communications
instruction exceeds the allowable
range.
• A second SFC program was started
with an instruction while an SFC
program was running.
Stop/
Action
continue
Stop/
• Check the detailed information
continue
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
Stop/
• Check the detailed information
continue
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and check if the
SP.DEVST instruction is used
correctly in the program.
• Execute the SP.DEVST instruction
again on another day, or change
the value in SD771.
• Set the value in SD771 within the
settable range.
Stop/
• Check the detailed information
continue
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the PID control
instruction structure.
Stop/
• Check and change the send data
continue
size of the CPU module or the
external device.
• If the same error code is displayed
again, the possible cause is a
hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
Stop/
• Check the detailed information
continue
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and check the SFC
program execution status.
Detailed
Diagnostic
information
timing
Error location
At instruction
information,
execution
process
control
instruction
processing
information
Error location
information
Error location
At instruction
information
execution
Error location
At instruction
information
execution
Error location
At instruction
information
execution
Error location
At instruction
information
execution