Mitsubishi Electric MELSEC iQ-R Series User Manual page 668

Process cpu module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

No.
Name
SM1654
Memory copy being
executed
SM1655
Memory copy
completion
SM1656
Auto memory copy
SM1673
Tracking transfer
completion flag
SM1679
Error reset (the other
system)
SM1680
Error of the other
system monitoring
SM1681
Latest self-diagnostic
error (including
annunciator ON) (the
other system)
SM1682
Latest self-diagnostic
error (not including
annunciator ON) (the
other system)
SM1683
Detailed information
1: Flag in use (the
other system)
SM1684
Detailed information
2: Flag in use (the
other system)
SM1754
Waiting for the start-
up of the other
system
SM1756
Wait timeout for
receiving cyclic data
after system
*1
switching
APPX
666
Appendix 4 List of Special Relay Areas
Data stored
Off: Not executed
On: Being executed
Off: Not completed
On: Completed
Off: Disabled
On: Enabled
Off: Transfer not completed
On: Transfer completed
OffOn: Standby system error reset
requested
OnOff: Standby system error reset
completed
Off: No error
On: Error
Off: No error
On: Error
Off: No error
On: Error
Off: Not used
On: In use
Off: Not used
On: In use
Off: Started up (own system)
On: Waiting for the start-up (the other
system)
Off: No timeout
On: Timeout
Details
• This relay is on during the memory copy from the
control system to the standby system.
• This relay turns off when the memory copy is
completed.
• This relay turns on at the completion of the memory
copy from the control system to the standby system.
• Initial value is off: Memory copy has not completed.
This relay turns on when the automatic memory copy
is set to enable.
• This flag is stored a result of the tracking transfer
operated in the preceding END processing.
• The flag turns on if any of the tracking transfers in
block 1 to 64 has been normally completed, and
turns off if the tracking transfers failed due to causes
such as tracking communication error.
• This relay is turned from off to on to clear a
continuation error occurred in the standby system.
• This relay turns from on to off when the error reset
has been completed.
• Initial value is off.
• This relay turns on if an error occurs on
communications with the other system when an
initial processing (including when the system is
determined while waiting for the other system starts
up) or an END processing is performed. (This relay
turns on when the bit of SD1648 turns on.)
• This relay turns off when an error is cleared.
• This relay turns on if a diagnostic error occurs in the
CPU module in the other system. (The relay also
turns on if an error is detected by an annunciator.)
• The SM0 status for the CPU module in the other
system is reflected.
• This relay turns on if a self-diagnostic error occurred
in the CPU module in the other system. (The relay
remains off if an error is detected by an
annunciator.)
• The SM1 status for the CPU module in the other
system is reflected.
• This relay turns on when there is detailed
information 1 for an error occurred in the CPU
module in the other system.
• The SM80 status for the CPU module in the other
system is reflected.
• This relay turns on when there is detailed
information 2 for an error occurred in the CPU
module in the other system.
• The SM112 status for the CPU module in the other
system is reflected.
• This relay turns on while waiting for the start-up of
the other system after powered on.
• This relay turns off under the following conditions.
 Own system starts up as the control system or
the standby system after succeeding in tracking
communications with the other system.
 Own system is started up as the control system
by a certain operation while waiting for the start-up
of the other system.
This relay turns on when the receipt of the cyclic data
after system switching is not completed within the
*2
cyclic data receipt waiting time
wait cyclic data receive after system switching is
enabled. This relay turns off when the timeout does
not occur.
Set by (setting
timing)
S (Status change)
S (Status change)/
U
S (Initial)
S (Status change)
U/S (Status
change)
S (Initial/every
END/system
switching)
S (Every END)
S (Every END)
S (Every END)
S (Every END)
S (Status change)
S (At system
switching)
while the setting to