36 ERROR CODES
584
36.4 List of Error Codes
Error details and cause
• The specified step exceeds the range
that can be used in the SFC program.
• The number of simultaneous active
block steps that can be specified in
the SFC program exceeds the
permissible value.
• The total number of simultaneous
active steps that can be specified in
the SFC program exceeds the
permissible value.
• A SET Sn/BLm\Sn and RST Sn/
BLm\Sn instruction were specified for
the self step in the step operation
output.
• Memory/Device Setting set in the
CPU parameters differ from those
assigned to the sequence programs,
FB programs, and global label setting
file. (After Memory/Device Setting
were modified, only the CPU
parameters were written to the CPU
module.)
• Even though no program is set in the
CPU parameters, multiple program
files exist.
• The program file is incorrect. Or, the
program file is not written properly.
• For the subroutine type FB, "Use MC/
MCR to Control EN" of "Inherent
Property" is set to "Yes".
• No program file exists.
• Two or more SFC programs were
executed.
Stop/
Action
continue
Stop
• Check the detailed information
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
• Turn on SM321 (Start/stop SFC
program) if it is off.
Stop
• Check the detailed information
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
Stop
• After Memory/Device Setting are
modified, write the sequence
program file(s), FB file(s), and
global label setting file together
with the CPU parameter file to the
CPU module.
• If no global label is used, delete
the global label setting file.
Stop
• Set a program in the CPU
parameter.
• Delete unnecessary program files.
Stop
• Write the program file to the CPU
built-in memory again.
• Set "Use MC/MCR in EN Control"
in "Inherent Property" of
subroutine-type FB to "No" and
write the program file to the CPU
built-in memory again.
• Replace the CPU module with the
one that supports the use of the
subroutine-type FB for which "Use
MC/MCR in EN Control" of
"Inherent Property" is set to "Yes".
Stop
• Check if the system parameter file,
CPU parameter file, and program
file exist.
• Write the system parameter file,
CPU parameter file, and program
file to the CPU built-in memory.
Stop
• Ensure that only one SFC
program is executed.
Detailed
Diagnostic
information
timing
Error location
At instruction
information
execution
Error location
At instruction
information
execution, at
SFC program
execution
At instruction
execution, at
SFC program
execution
At instruction
execution
Drive/file
At power-on, at
information
RESET, at
STOP  RUN
state
Drive/file
At power-on, at
information
RESET, at
STOP  RUN
state
Drive/file
At power-on, at
information
RESET, at
STOP  RUN
state
Drive/file
At power-on, at
information
RESET, at
STOP  RUN
state
Drive/file
At SFC
information
program
execution