36 ERROR CODES
596
36.4 List of Error Codes
Error details and cause
• In a redundant system with redundant
extension base unit, the number of
slots on the main base unit differs
between system A and system B.
• In a redundant system with redundant
extension base unit, the module
mounting status of each slot or the
models of the modules used differ
between system A and system B.
• In a redundant system with redundant
extension base unit, the module
model name set in the system
parameters ("I/O Assignment
Setting") differs between system A
and system B.
(The error is detected in the control
system or the standby system.)
• In a redundant system with redundant
extension base unit, the main base
units in both systems are not
connected to the same redundant
extension base unit. (The error is
detected in the control system or the
standby system.)
• In a redundant system with redundant
extension base unit, an unsupported
extension base unit is connected to
the second or later extension levels.
(The error is detected in the control
system.)
• The redundant function module was
mounted next to the control CPU set
to process mode.
• The range set for tracking transfer in
the CPU parameters exceeds the
device range or the file register
capacity set in the CPU parameters.
Stop/
Action
continue
Stop
• Use the main base units with the
same number of slots in both
systems.
• Match the module mounting status
of each slot and the models of the
modules used on the main base
unit between the systems, and
restart the CPU module.
• Set the system parameters ("I/O
Assignment Setting") so that the
parameters in both systems are
the same.
Stop
• Connect both main base units to
the same redundant extension
base unit.
Stop
• Remove the unsupported
extension base unit. If all the
extension base units are
supported, the possible cause is a
hardware failure of the CPU
module or extension base unit.
Please consult your local
Mitsubishi representative.
Stop
• Set the CPU module to redundant
mode, and restart the system. Or,
remove the redundant function
module, and restart the system. If
the same error code is displayed
again, the possible cause is a
hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
Stop
• Check the detailed information
(parameter information) of the
error by executing module
diagnostics using the engineering
tool, correct the parameter setting
corresponding to the displayed
number, and take the following
actions:
(1) Check and correct the tracking
transfer settings in the CPU
parameters so that they will be
within the device range or the file
register capacity.
(2) Check and correct the device
settings or the file register
capacity setting in the CPU
parameters.
Detailed
Diagnostic
information
timing
System
At power-on, at
configuration
RESET
information
At power-on, at
RESET, at
tracking cable
connection
System
At power-on, at
configuration
RESET
information
System
At power-on, at
configuration
RESET, at
STOP  RUN
information
state
Parameter
At power-on, at
information
RESET