Error
Error name
Error details and cause
code
3101H
Program error
• The program contains a dedicated
SFC program instruction even
although it is not an SFC program.
3120H
Program error
• The CPU module does not support
the dedicated instruction executed.
3121H
Program error
• The number of devices used in the
dedicated instruction specified in the
program is incorrect.
3122H
Program error
• The function block or function
specified in the program does not
exist.
3140H
END instruction
• The END (FEND) instruction does not
error
exist in the program.
Stop/
Action
continue
Stop
• Check the detailed information
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
• Take measures to reduce noise.
• Write the sequence program(s)
and FB program(s) to the CPU
module again. Then, reset the
CPU module and run it again. If
the same error code is displayed
again, the possible cause is a
hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
Stop
• Check the detailed information
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
• Check the firmware version of the
CPU module and use a supported
product.
Stop
• Check the detailed information
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
Stop
• Check the detailed information
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
• Take measures to reduce noise.
• Write the sequence program(s)
and FB program(s) to the CPU
module again. Then, reset the
CPU module and run it again. If
the same error code is displayed
again, the possible cause is a
hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
Stop
• Check the detailed information
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
• Take measures to reduce noise.
• Write the sequence program(s)
and FB program(s) to the CPU
module again. Then, reset the
CPU module and run it again. If
the same error code is displayed
again, the possible cause is a
hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
Detailed
Diagnostic
information
timing
Error location
At write, at
information
power-on, at
RESET, at
STOP  RUN
state
Error location
At power-on, at
information
RESET, at
STOP  RUN
state, at
instruction
execution
Error location
At instruction
information
execution
Error location
At instruction
information
execution
Error location
At power-on, at
information
RESET, at
STOP  RUN
state
36 ERROR CODES