Mitsubishi Electric MELSEC iQ-R Series User Manual page 559

Process cpu module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error name
Error details and cause
code
1830H
Receive queue
• The number of transient receive
full
request exceeded the upper limit of
simultaneously processable requests.
1831H
Receive
• Transient reception failed.
processing error
1832H
Transient data
• Too much transient transmission
error
processing exists and transient
transmission cannot be performed.
1845H
Transient data
• Too much transient transmission
buffer full
processing exists and transient
transmission cannot be performed.
1860H
Network error
• Tracking communications stopped
due to an error in the network or in the
redundant function module.
1861H
Tracking
• Tracking communications could not
communication
be performed successfully due to an
error
error in the network or in the
redundant function module.
1900H
Constant scan
• The scan time exceeded the constant
time error
scan time set in the CPU parameters.
1B00H
Network
• The CC-Link IE Field Network
configuration
configuration differs between the
mismatch
systems A and B. (The error is
detected in the standby system.)
1B20H
System
• The operating status of the CPU
consistency
module differs between the systems A
check error
and B. (The error is detected in the
(operating
standby system.)
status)
1B40H
Redundant
• Both systems were found to be set as
system error
system A or system B when tracking
cables were connected. (The error is
detected in the control system or the
standby system.)
1B42H
Redundant
• The CPU module operated in
system error
redundant mode was connected to
the CPU module set to process mode
with tracking cables. (The error is
detected in the control system or the
standby system.)
Stop/
Action
continue
Continue
• Reduce the frequency of transient
transmission, and perform
transmissions again.
• Increase the frequency of
transient transmission by using
the COM instruction.
Continue
• Reduce the frequency of transient
transmission, and perform
transmissions again.
Continue
• Correct the number of transient
transmission executions.
Continue
• Correct the number of transient
transmission executions.
Continue
• Check the network status by
executing module diagnostics
using the engineering tool and
take an action.
• If the error code is displayed again
even after taking an action, please
consult your local Mitsubishi
representative.
Continue
• Check and correct the constant
scan time setting.
Continue
• Check that all network cables are
connected correctly.
• Take measures to reduce noise.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
network cable. Please consult
your local Mitsubishi
representative.
Continue
• Set the same operating status to
the CPU modules in both systems.
Continue
• Set one system as system A and
the other system as system B by
performing online operation. Then,
restart the CPU modules in both
systems.
Continue
• Read the project stored in the
CPU module operated in
redundant mode, and write it to
the CPU module set to process
mode. Then, reset the CPU
module set to process mode, and
run it again.
Detailed
Diagnostic
information
timing
Always
System
Always
configuration
information
Always
Always
Always
Time
At END
information
instruction
execution
System
Always
configuration
information
Always
Always
Always
36 ERROR CODES
557
36.4 List of Error Codes